Skip to main content

1109010

FDR100-EZ Addressable Reflective Beam Detector, 100 m
  • Single installation and maintenance point
  • Fully addressable
  • 100 m detection range
  • Unique simple alignment
  • Selectable alarm thresholds
View all

At a glance

General

The FDR100-EZ linear beam smoke detector is developed for use in areas where point type detectors would be difficult to install and maintain. The FDR100-EZ has a detection ranges of up to 100 m.

A transmitter and receiver are contained in one enclosure. The transmitter emits an invisible infrared beam, which is reflected back to the receiver, by a prism mounted directly opposite and in clear line of sight. The presence of smoke obscures the beam and reduces the signal strength detected at the receiver.

Unique Alignment

Alarm thresholds of 25%, 35% and 50% obscuration are selectable, making the detector suitable for a wide range of building environments. The fire output can be set to latch, only cancelled by resetting the device, or auto reset where the detector is reset automatically 5 seconds after the received infrared signal has recovered to a level above the alarm threshold.

The detector and the reflecting prism are installed on opposite walls of the protected area, usually between 0.3 and 0.6 m below ceiling height. With unique alignment features, the equipment is easy to install, provides high stability and freedom from false alarms.

Continuously monitored

The FDR100-EZ incorporates continuous monitoring of both electrical and optical faults. If the infrared beam is obscured rapidly to a level above 90%, for approximately 10 seconds the condition is seen as a fault. Long-term degradation of signal strength is monitored and adjusted automatically.

Installed under flat horizontal ceilings, a single unit provides satisfactory smoke detection up to 7.5 m on either side of the beam axis. For larger areas multi detector systems can be installed.

The FDR100-EZ addressable detector is connected directly to the ZP3 loop wiring and is configured with it’s own address which the control panel poles every two seconds.

Details

  • Single installation and maintenance point
  • Fully addressable
  • 100 m detection range
  • Unique simple alignment
  • Selectable alarm thresholds
  • Latching or auto reset fire output
  • Automatic contamination compensation

Technical specifications

General
Status indication
Fire, fault , power on & alignment
User interface
LEDs
Compatibility
ZP7 Series Systems
Connectivity
2 Wire loop
Reset Via ZP loop
Electrical
Operating voltage
10.2 to 30 VDC
Current consumption
<5 mA (Quiescent with no LEDs illuminated)
<15 mA (Alarm)
Detection
Detection principle
Optical (Light Scatter)
Monitoring
Adjustment limit exceeded
Signal lost
Signal strength
Coverage area
<1500 m­­²
Zone length
100 m
Range
100 m
Lateral detection
15 m
Output
Output quantity
2
Output type and rating
Fire – N/O, closes on fire. Fault – N/C, opens on fault
Physical
Physical dimensions
130 x 210 x 120 mm (W x H x D)
Net weight
740 g
Colour
White enclosure, black - lens cover
Mounting type
Wall mount
Material Chassis – steel, Enclosure – flame retardant ABS
Environmental
Vandal proof
No
Operating temperature
-30°C to +55°C
Storage temperature
-30°C to +55°C
Relative humidity
0 to 95% noncondensing
Environment
Indoor
IP rating
IP50 (EN60529)
Regulatory
Compliancy
CE
REACH
RoHS 2
Certification
CPR
Standards
EN54-12
Environmental
EEC89/336