Skip to main content

9-30051

Wire burn test unit
  • Testing to BS5839 and BS6266
  • Fuse protected
View all

At a glance

General

The unit is used to test very early warning aspirated smoke detection equipment. The unit provides a 6.3 VAC output from 230 VAC mains supply. High current is passed through a test wire in order to heat it, which causes its insulation to burn giving off smoke.

Commissioning

During the commissioning of an ASD system, the hot wire test unit should be used. The unit must be placed on the ground in the protected area and then activated. The wire which is heated will generate smoke which simulates a real fire in the protected area. The smoke generated will then rises and create a smoke plume similar to a real fire. In this way the ASD can be tested to confirm that it is performing as designed, while taking into account factors like air flow and other environmental factors.

Routine maintenance

To ensure that the ASD is still performing as designed, it is recommended to do a hot wire test as part of the routine maintenance. This might not be possible in all installations due to the nature of the protected area. For example if the protected area is used for food preparation, then it would not be suitable. The hot wire test will confirm both the rising of smoke and formation of a plume, as well as the ASD’s performance to detect smoke and raise an alarm.

Details

  • Testing to BS5839 and BS6266
  • Fuse protected

Technical specifications

Electrical
Operating voltage
230 VAC, 50 Hz, 1A
Output transmitter power
6.3 VAC, 16.6 A
Environmental
Environment
Indoor
IP rating
IP30
Regulatory
Certification
EN54-20
Operating time
Maximum on time 3 min.
Minimum off time 7 min.

Downloads

All downloads

Datasheet

Installation sheet

Certificates

If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.