Skip to main content

9-30725

AirSense Stratos Micra 10 High Sensitivity Smoke Detector
  • Ultra small low cost aspirating smoke detector for easy and discreet installation
  • High sensitivity provided by laser based forward light scatter for reliable early warning
  • Single sampling pipe up to 50m in length (still air)
  • Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
View all

At a glance

Description

The AirSense Micra 10 is designed to provide very high sensitivity smoke detection in a small package.

ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.

The detector is designed to fit into a Docking Station. All sampling pipes and cables are connected to the Docking Station as a first fix operation leaving the detector to be fitted during the final commissioning phase if required. This ensures that detectors are less likely to be damaged during the installation.

Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.

Typical Applications

• Data storage units
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms

Options Available

• Addressable Protocol Interface Cards APIC™ available
• Relay expansion card


Details

  • Ultra small low cost aspirating smoke detector for easy and discreet installation
  • High sensitivity provided by laser based forward light scatter for reliable early warning
  • Single sampling pipe up to 50m in length (still air)
  • Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
  • CPR approved

Technical specifications

General
Status indication
LED
Alarm levels
4 (Aux, Pre-alarm, Alarm and Alarm 2)
Electrical
Operating voltage
21.6 to 26.4 VDC
Current consumption
250 mA
Detection
Detection principle
Laser light scattering mass detection and particle evaluation
Range
0.3% to 25% (%Obs/m)
Particle sensitivity range
0.003μ to 10μ
Sampling pipe
Length
50 m maximum run (25 m in moving air)
Inlet quantity
1
Exhaust
1 (optional)
Output
Output quantity
2 - Alarm (n/o) and Fault (n/c)
Output type and rating
500 mA @ 30 V
Physical
Physical dimensions
145 x 220 x 85 mm (W x H x D)
Net weight
1.7 kg
Colour
Cream
Cable entries
2 x M20
Material (body)
Sheet steel enclosure
Environmental
Operating temperature
-10 to +60°C (EN54-20)
Relative humidity
0 to 90% noncondensing
Environment
Indoor
IP rating
IP40
Regulatory
Certification
EN54-20
Sampling pipework
Diameter 27mm OD
Amount of Class A holes (high sensitivity) up to 2 holes
Amount of Class B holes (enhanced sensitivity) up to 4 holes
Amount of Class C holes (normal sensitivity) up to 10 holes
Outputs
Expansion Optional input and relay card
Networking
SenseNET (RS-485) Not supported