Skip to main content

ZP732-2P

Ziton series Addressable Dual Detector (Optical & Heat), Polar White
  • Senses both smoke and heat
  • Heat only facility
  • Smoke element complies with EN54 Part 7 and CEA4021
  • Heat element complies with EN54 Part 5 Class A1 and A2
  • Analogue sensing - reduces false and unwanted alarms
View all

At a glance

Wide response range

Designed to provide the earliest response to a wide range of fire types, the ZP732-2P POLAR WHITE dual detector combines optical smoke sensing and thermal monitoring to provide an accurate warning of fire. Individual software monitoring of each element measures actual smoke levels, in addition to temperature rates of rise. Smoke sensing can be isolated for areas where ambient smoke may exist at certain times of the day, or used on a day night basis in premises where heat only is required whilst the building is occupied.

Temperature response meets the requirements of EN54 Part 5 (Class A1 and A2), with smoke sensitivity complying with EN54 Part 7 and test procedure CEA4021. Several international approval bodies approved this detector.

Automatic self test

The smoke element is regularly recalibrated by the panel for contamination and constant sensitivity. Self test and selectable alarm verification are all provided automatically by the ZP control panel software.

Up to 127 sensing devices may be connected to each of the control panel loops. All loop devices incorporate switch settings enabling them to be assigned a unique address, which is polled by the panel every two seconds.

Whilst effective in operation, the ZP732-2 is unobtrusive when installed. The low profile moulding makes the unit ideal for both commercial and industrial interiors. A red LED indicator, situated on the sensor moulding, flashes to indicate when the unit is in alarm.

Locking base option

For ease of removal these detectors plug into a range of base units by a simple twist and lock action. A site selectable option is provided to lock the sensor into its base. Once applied the unit can only be removed by means of a special tool.

Space for address labels is provided on detector and base mouldings, ensuring that units are replaced in their correct location. The address numbers can be identified from floor level.

Details

  • Senses both smoke and heat
  • Heat only facility
  • Smoke element complies with EN54 Part 7 and CEA4021
  • Heat element complies with EN54 Part 5 Class A1 and A2
  • Analogue sensing - reduces false and unwanted alarms
  • Addressable - system knows the status and location of every detector

Technical specifications

General
Status indication
Alarm LED (red)
Compatibility
ZP7 Series Systems
Connectivity
2 Core loop or spur & remote indicator
Addressing method
DIP Switches
Addressing method 7 way dipswitch
Electrical
Operating voltage
19.5 to 20.5 V (Loop powered)
4 V (Max. line loss)
Current consumption
<600 μA (Quiescent)
<700 μA (Active)
Detection
Detection principle
Photo electric light scatter or heat
Monitoring
Device type
Open circuit
Presence
Short circuit
Coverage area
100 m² (Optical)
50 m² (Heat)
Output
Output quantity
1
Remote alarm output
Yes
Physical
Physical dimensions
106 x 58 mm (Ø x H)
Net weight
105 g (excluding base)
Colour
Polar white
Mounting type
Base mount
Material (body)
Moulded ABS
Mounting Plugs into surface or semi recessed base
Environmental
Vandal proof
No
Operating temperature
-10 to +85°C
Storage temperature
-20 to +70°C
Relative humidity
20 to 95% noncondensing
Environment
Indoor
IP rating
IP32
Regulatory
Compliancy
CE
REACH
RoHS 2
WEEE
Certification
CPR
Standards
EN54-5, EN54-7
Environmental
EEC89/336