Ziton series point detector base with isolator
- Provides short circuit loop protection for up to 127 devices on the loop
- LED indication of isolation activation
- Optional base lock facility
- Complies to the recommendation of BS5839-1
- Backwards compatible with legacy base and standalone isolators
Related products
At a glance
Product overview
The ZP7-IB2-P isolator base protects Ziton addressable fire detection loops against short circuits. Up to 127 base isolators may be connected to each loop when this isolator is used in enhanced mode. For legacy systems the ZP7-IB2-P also support the old operating modes and are therefore backwards compatibility with legacy isolators.
Just as with a standard base, the ZP7-IB2-P allows the detector to be removed or replaced without disconnecting loop wiring from the detector.
Regulatory Loop Protection
The ZP7-IB2-P is intended for use on Class-A, return loop wiring configurations. By regulation a zone of no more than 32 fire alarm devices must be located between isolators. In the event of a short circuit fault the isolators on either side of the fault disconnects the section of cable between them. Devices inside the zone get disconnected, but devices outside the disconnected zone continue to operate normally.
The ZP7-IB2-P meets the recommendations for loop monitoring in local codes like BS5839-1.
Isolator design
With the improved design of the ZP7-IB2-P it is now possible to ensure that no devices are disconnected from the isolated section of cable, that could be a small as the cable between two isolator bases. Every detector may be fitted with an isolator base, ensuring maximal device operation even in the event of a cable short circuit.
Additional advantages
Adding ZP7-IB2-P isolator bases has no affect on device addressing for that loop as they require no addressing. A selectable lock facility is provided to lock the detector into the base preventing removal without a special tool.
Situated on the base moulding, an yellow LED indicator flashes when the isolator is activated.
Details
- Provides short circuit loop protection for up to 127 devices on the loop
- LED indication of isolation activation
- Optional base lock facility
- Complies to the recommendation of BS5839-1
- Backwards compatible with legacy base and standalone isolators
Technical specifications
| General | ||
|---|---|---|
| Status indication |
LED (yellow)
|
|
| Compatibility |
All ZP addressable systems
|
|
| Connectivity |
2-wire loop
|
|
| Addressing method |
No addressing required
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Loop powered
|
|
| Operating voltage |
16 to 20 VDC
|
|
| Current consumption |
180 µA (quiescent)
230 µA (activated - legacy mode)
4 mA (activated - enhanced mode)
|
|
| Cable specification |
Class-A return loop (loop resistance <75 Ω)
|
|
| No. of cable cores |
2
|
|
| Terminals |
8
|
|
| Detection | ||
|---|---|---|
| Monitoring |
Short circuit
|
|
| Isolation | ||
|---|---|---|
| Type |
Negative line break
|
|
| Quantity per loop |
≤16 (legacy mode)
≤127 (enhanced mode)
|
|
| Series resistance |
<0.060 Ω
|
|
| Impedance requirements |
<16 Ω (between panel and first isolator)
<16 Ω (between adjacent isolators)
<16 devices between adjacent isolators
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
109 x 23 mm (Ø x H)
|
|
| Net weight |
79 g
|
|
| Colour |
Polar white
|
|
| Mounting type |
Surface mount
|
|
| Cable entries |
1
|
|
| Material (body) |
Moulded thermoplastic
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +55°C
|
|
| Storage temperature |
-10 to +55°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP21
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 2
WEEE
|
|
| Certification |
CPR
EN54-17
|
|
Downloads
All downloadsDatasheet
Installation sheet
Technical documentation
Certificates
Other EU certificate
Other EU certificate
VMC_APF-1807_ZP-2
Other EU certificate
VMC_APF-1862_ZP7-IB2-P
Other EU certificate
VMC_PR-2017/064_ZP2-A series
Other EU certificate
VMC_PR-1936/064_Ziton ZP-2 (2010-2 series)
Other EU certificate
VMC_PR-1751/064_ZP-2 (2010-2 series)
Other EU certificate
VMC_APF-1326_ZP2
CPD / CPR
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.