Skip to main content

99202

A45E-2 A-series EN mini interface
  • Addressable input interface unit
  • Low profile
  • DIN rail mounted
  • Supervises normally open input circuits
  • Monitors input circuit wiring for open or short circuit faults
View all

Related products

At a glance

Overview

The A45E-2 addressable interface (input unit) and is designed for installation within the enclosures of equipment associated with fire detection systems. The unit is installed directly onto the ZP loop wiring, carries a system address and enables signals from associated equipment to be interfaced into the fire alarm system. Input signals are fully displayed at the control panel and can be programmed to activate any system output.

By routing loop wiring and installing interfaces adjacent to input equipment, system integrity is increased and the need for long spur wiring between equipment terminals and the fire alarm interface is eliminated.

Installation and mounting options

Approved to EN54-18, the A45E-2 can be installed singly, or used in groups to provide multiway inputs from equipment such as volt free, zonal outputs from conventional fire alarm systems or flow valves from sprinkler installations. Housed in a low profile, single width moulding the interface is designed to clip directly onto a standard DIN rail fixing or be installed in a SMB-DIN1 box (two unit capacity), or a SMB-DIN2 box (four unit capacity).

Installed as part of an addressable system, up to 127 line devices (detectors, call points or interface units) may be connected to each of the control panel loops. All loop devices incorporate switch settings enabling them to be assigned a unique address which is polled by the panel every two seconds.

LED indication

A red LED indicator positioned on the front moulding flashes when the interface has operated, providing clear identification of the input signal source.

Details

  • Addressable input interface unit
  • Low profile
  • DIN rail mounted
  • Supervises normally open input circuits
  • Monitors input circuit wiring for open or short circuit faults
  • Approved to EN54:18 and CPR certified

Technical specifications

General
Status indication
LED (red) flashing on operation
Compatibility
All ZP addessable systems
Addressing method
DIP Switches
Address range
1 to 127
Electrical
Power supply type
Loop powered
Operating voltage
Pulsed 19.5 to 20.5 V, line drop < 4 VDC
Current consumption
600 µA (quiescent)
700 µA (alarm)
Input
Input quantity
1
Input type and rating
Supervised
Input states
Active
Normal
Open
Short
Alarm resistor
1.8 kΩ
Termination resistor
3.9 kΩ
Cable specification < 10 m (from switching terminals)
Physical
Physical dimensions
45 x 78 x 28 mm (W x H x D)
Net weight
40 g
Colour
White
Mounting type
DIN-rail
Wall mount
Material
Moulded ABS
Cable specification
2 core (screened)
Environmental
Vandal proof
No
Operating temperature
-10 to +55°C
Storage temperature
-10 to +55°C
Relative humidity
20 to 95% noncondensing
Environment
Indoor
IP rating
IP20
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-18