ZX432-2P
Wireless optical heat head to work with ZR401-3 base & battery pack, polar white
- No external aerials
- Dual battery supply via base
- Full device status monitoring – power sources, head removal and device tamper
- Senses both smoke and heat
Related products
At a glance
General
The ZX432-2P is a wireless, POLAR WHITE addressable multisensor head capable of operating in optical, temperature or multisensor, optical/heat modes.
Product works with ZR401-3
Fast response to a wide range of fires
Designed to provide the earliest response to a wide range of fire types in locations where hard wiring is not an option, ZX432-2 detectors combine optical smoke sensing and thermal monitoring to provide an accurate warning of fire. Smoke sensing may be isolated for areas where ambient smoke may exist at certain times of the day, or used on a day night basis in premises where heat only is required whilst the building is occupied.
Detector control
The ZX432-2 detector is controlled from the main control panel via a wireless base and loop wired radio interface module allowing both wireless and hardwired devices to be seamlessly located and controlled from the same wiring loop. Every wireless device controlled through the radio loop module, is assigned its own IDENT address with which the main control panel communicates, providing the same system facilities as directly wired devices.
System operation
Temperature and smoke sensitivity may be set by a selection of switches located in the base of the ZX432-2. Calibration and self-testing are carried out automatically.
Removal or replacement of an incorrect sensing devices are identified by the system and details displayed at the main control panel. Sophisticated auto contamination adjustment compensates for any long-term drift in performance caused by dirt entering the sensing chamber.
For ease of removal, ZX432-2 detectors plug into the radio base by a simple twist and lock action.
Removal or replacement of an incorrect sensing devices are identified by the system and details displayed at the main control panel. Sophisticated auto contamination adjustment compensates for any long-term drift in performance caused by dirt entering the sensing chamber.
For ease of removal, ZX432-2 detectors plug into the radio base by a simple twist and lock action.
Certification
The ZX432-2 temperature response meets the requirements of European Standard EN54 Part 5 (settable to class A or class B), with smoke sensitivity complying with EN54 Part 7. The ZR432-2 is approved to EN54:5, EN54:7 , and carries CPD certification.
Details
- No external aerials
- Dual battery supply via base
- Full device status monitoring – power sources, head removal and device tamper
- Senses both smoke and heat
Technical specifications
| General | ||
|---|---|---|
| Status indication |
Red alarm LED
|
|
| Wireless frequency |
868 MHz
|
|
| Compatibility |
All ZP addressable systems via RLM
|
|
| Addressing method |
Unique address embedded
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Batteries
|
|
| Batteries |
Batteries in base
|
|
| Operating voltage |
3 VDC
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Smoke element - Photoelectric light scatter Heat element - Thermistor
|
|
| Monitoring |
Continuously self-checking
|
|
| Coverage area |
Smoke element - <100m², Heat element - <50 m² (Subject to local regulations)
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
106 x 75 mm (including base) (Ø x H)
|
|
| Net weight |
350 g (including base & batteries)
|
|
| Colour |
Polar white
|
|
| Mounting type |
Surface mount
|
|
| Material (body) |
Moulded ABS
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-10 to +60°C
|
|
| Storage temperature |
-20 to +70°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP32
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
CPR
REACH
RoHS
|
|
| Certification |
CPD
EN54-5
EN54-7
|
|
Downloads
All downloadsDatasheet
Certificates
CE
DoC - EC Declaration of Conformity
DoP
DoP 0359-CPR-0128
Non EU certificate
VMC_UAE_APF-1324_ZR432
DoC
KGS F&S - DoC_10-4213-356-0199_ZX432-2P
DoP
KGS F&S - DoP_360-4213-0199_ZX432
CPD / CPR
CPD / CPR
Certificate of Constancy of Performance (EN54-3, EN54-25)
CPD / CPR
Certificate of Constancy of Performance (EN54-25)
CPD / CPR
CPR_0370-CPR-1818_ZX432-2P
Other EU certificate
Installation sheet
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.