A70 conventional interface
  • Interfaces conventional devices to an addressable loop
  • Standard and intrinsic safe detector support
  • Status reporteds 2 seconds
  • Open, short and head-out supervision
  • DIN35 rail mounted
View all

At a glance

General

The A70E-2 is a ZP7 series, addressable interface for conventional fire detectors. It is fully loop powered and enables existing or new conventional fire detection zones to be interfaced to an addressable fire alarm system, allowing all areas of a site to be controlled by a Ziton addressable fire panel.

Via the A70E-2 each conventional zone is assigned a unique loop address. The zones are monitored for alarm and fault conditions and the status reported to the fire panel every 2 seconds.

Up to 15 Ziton Z600 series conventional devices can be connected to the interface, taking a single address on the loop. The Ziton protocol supports up to 127 addresses per loop.

Detector Head-out Removal Monitoring

The A70E-2 monitors its conventional zone wiring for open and short circuit faults via end-of-line resistors supplied with the unit. When Z600 detectors are installed with Z6-BS5 bases, the interface maintains complete operation of all zone devices even when a detector is removed from its base.

For maintenance purposes, clear visual indications are shown on the front of the A70E-2 for alarm (red LED) and fault (amber LED).

Multiple Application Support

Drawing its power directly from the fire detection loop and supporting low current consumption, the A70E-2 has additional system applications ranging from an interface to equipment for hazardous areas, the operation of magnetic door retainers (via an interposing relay) and even an interface for linear beam detectors.

Housed in a low profile housing, the A70E-2 is designed to clip directly onto a standard DIN35 rail fixing, or be installed in an optional housing (SMB-DIN1 - one unit capacity, or a SMB-DIN2 - two unit capacity). In systems where numerous interfaces are installed or current requirement is excessive, the A70E-2 can be powered from an external. EN54-4 approved power supply.

Details

  • Interfaces conventional devices to an addressable loop
  • Standard and intrinsic safe detector support
  • Status reporteds 2 seconds
  • Open, short and head-out supervision
  • DIN35 rail mounted
  • Up to 127 conventional zones interfaced to a ZP loop (with external PSU)
  • EN54:18 approved and CPR certified

Technical specifications

General
Compatibility
ZP2 and ZP3 addressable systems
Electrical
Operating voltage
Loop 19.5 to 20.5 VDC
external 19 to 30 VDC
Current consumption
7.3 mA (quiescent) (ext. power)
<36.6 mA (alarm) (ext. power)
8.3 mA (quiescent) (loop powered)
<24.6 mA (alarm) (loop powered)
Physical
Physical dimensions
85 x 78 x 27 mm (W x H x D)
Net weight
80 g
Colour
White
Mounting type
DIN-rail
Surface mount
Material
Moulded ABS
Environmental
Operating temperature
-10 to +80°C
Relative humidity
20 to 95% noncondensing
Environment
Indoor
IS
IP rating
IP20
Regulatory
Certification
EN54-18
Wiring
Addressable loop Two core screened
Conventional zone Two core
Monitoring
Open & short circuit fault
Conventional support
<15 detectors
Detector compatibility
UTC supplied conventional, IS detectors & barrier
End-of-line support
Standard devices 3k9 Ω
Intrinsically safe devices 8k2 Ω