ZPR868
Ziton series Addressable 868 MHZ - Radio Loop Module (RLM)
- Programmable to suit protected area
- Automatic selection from 32 radio channels for reliable signalling
- Multipath technology ensures a robust radio solution
- Diversity transceivers allow maximum operational range
- Complies with EN300-220
Related products
At a glance
General
The ZPR868 is a Ziton protocol, radio loop module for interfacing a zone of wireless 868 MHz Ziton fire alarm devices into a ZP fire alarm system. It enables these wireless devices to be controlled directly from the ZP hardwired loop, and provides a seamless interface between the hardwired components and the wireless devices.
System design
The ZPR868 comprises of a radio transceiver capable of receiving 31 radio devices. An LCD display is provided along with function buttons to allow programming and diagnostics to be carried out for associated devices. The interface is addressed on the loop via its onboard 8 way DIP switch. A total of 2 ZPR868 units may be fitted onto a single fire alarm control panel loop controlling up to 62 wireless loop devices.
Seamless addition of wireless devices
Every wireless device controlled through the ZPR868 has its own unique address with which the main fire alarm control panel communicates with it, providing the same system capabilities as directly wired devices. A full range of wireless detection and alarm devices is available, including multi-sensors capable of dual sensing heat and smoke, smoke only or heat only configurations, manual call points, notification devices (sounders & beacons) as well as input/output units.
Full flexibility
Wireless devices are featured in many fire detection and alarm systems, specified where the installation of hard wiring would be difficult or impossible to complete, decorative finishes to the interior of the protected building preclude wiring runs or where the time scales to complete installation are minimal. The ZPR868 allows the system designer full flexibility in selecting which devices on the loop are to be hardwired and which are to be wireless.
Details
- Programmable to suit protected area
- Automatic selection from 32 radio channels for reliable signalling
- Multipath technology ensures a robust radio solution
- Diversity transceivers allow maximum operational range
- Complies with EN300-220
- EN54-17,18, 25 and CPR certified
Technical specifications
| General | ||
|---|---|---|
| Status indication |
16 character LCD display
|
|
| Wireless frequency |
868 MHz
|
|
| Compatibility |
Ziton ZP7 series addressable systems
|
|
| Electrical | ||
|---|---|---|
| Operating voltage |
16 to 22 VDC
|
|
| Current consumption |
26 mA (typical)
77 mA (max.)
|
|
| Configuration | <2 Radio devices per loop | |
| Output transmitter power | Variable 0-14 dBm | |
| Isolation | ||
|---|---|---|
| Series resistance |
0.8 Ω
|
|
| Switch current |
0.8 A
|
|
| Leakage current |
0.2 A
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
270 x 205 x 75 mm (W x H x D)
|
|
| Net weight |
950 g
|
|
| Colour |
Grey (Pantone 428c)
|
|
| Mounting type |
Wall mount
|
|
| Material |
Plastic
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +50°C
|
|
| Storage temperature |
-20 to +60°C
|
|
| Relative humidity |
0 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP54
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS
WEEE
|
|
| Certification |
CPR
|
|
| Standards |
EN54-17, EN54-18, EN54-25, ETSI 300-220
|
|
Downloads
All downloadsDatasheet
Installation sheet
Certificates
CE
DoC - EC Declaration of Conformity
DoP
DoP 0359-CPR-0224
Non EU certificate
Non EU certificate
ICASA - TA-2025/2372
CPD / CPR
Configuration manual
Configuration manual
Ziton Radio Loop Module Commissioning Guide
Configuration manual
Ziton Radio Loop Module Programming Guide
Other EU certificate
Other EU certificate
VMC_PR-2017/064_ZP2-A series
Other EU certificate
VMC_PR-1751/064_ZP-2 (2010-2 series)
Other EU certificate
VMC_APF-1326_ZP2
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.